You’re about to download 6.07.0

The main changes implemented since the last version are as follows:

PM compatibility: 1.25.0

New features:

  • EIC: Added Cummins KTA19, Deutz EMR5 Stage V and Perkins Stage V.
  • EIC: Added configurable TSC1 transmission rate and checksum/counter for Generic J1939.
  • EIC: Enable/disable alarm ack. via J1939 (DM11).
  • Extended RMI 20 Points in multi-inputs.
  • Extended mA 17 Points in multi-inputs.
  • M-Logic flags for Enable / Disable for spinning reserve added.
  • Dynamic Frequency Response mode for controlling frequency in situations with excessive amounts of PV-power, added for single generator.
  • Extended EIC wait to start (preheat) support. Introduced M-logic command to inhibit wait to start.
  • EIC: Added support of Scania EMS2 S8 HC Evaporation Status in M-logic and view.
  • Selection of Gov reference for ECU added in menu 15100. Select between nominal frequency or nominal rpm.

Corrections:

  • N + X ON/OFF via digital input or M-Logic corrected.
  • EIC autoviews is not deleted doing power up.
  • Q(U) U-shift regulation could assign a Q reference different than 0 to the AVR regulator when the voltage was inside the deadband. This has been fixed.
  • GOV output was sometimes raising to 100% when GB was closed with static sync. This has been fixed.
  • A genset will now charge a battery with the correct amount during negative PMS setpoints.
  • A genset will now calculate the correct power reference if a battery operating as a energy source is charging from excess PV power.
  • A running DG with its GB closed could react to invalid power management data when changing from a single DG application to a standard application.
  • A mains could issue a start signal to DGs based on invalid power management data when a BTB was powercycled.
  • Idle run stops engine correctly when using Low speed.
Ver. Date Description

6.07.0

11/07/2022

PM compatibility: 1.25.0

New features:

  • EIC: Added Cummins KTA19, Deutz EMR5 Stage V and Perkins Stage V.
  • EIC: Added configurable TSC1 transmission rate and checksum/counter for Generic J1939.
  • EIC: Enable/disable alarm ack. via J1939 (DM11).
  • Extended RMI 20 Points in multi-inputs.
  • Extended mA 17 Points in multi-inputs.
  • M-Logic flags for Enable / Disable for spinning reserve added.
  • Dynamic Frequency Response mode for controlling frequency in situations with excessive amounts of PV-power, added for single generator.
  • Extended EIC wait to start (preheat) support. Introduced M-logic command to inhibit wait to start.
  • EIC: Added support of Scania EMS2 S8 HC Evaporation Status in M-logic and view.
  • Selection of Gov reference for ECU added in menu 15100. Select between nominal frequency or nominal rpm.

Corrections:

  • N + X ON/OFF via digital input or M-Logic corrected.
  • EIC autoviews is not deleted doing power up.
  • Q(U) U-shift regulation could assign a Q reference different than 0 to the AVR regulator when the voltage was inside the deadband. This has been fixed.
  • GOV output was sometimes raising to 100% when GB was closed with static sync. This has been fixed.
  • A genset will now charge a battery with the correct amount during negative PMS setpoints.
  • A genset will now calculate the correct power reference if a battery operating as a energy source is charging from excess PV power.
  • A running DG with its GB closed could react to invalid power management data when changing from a single DG application to a standard application.
  • A mains could issue a start signal to DGs based on invalid power management data when a BTB was powercycled.
  • Idle run stops engine correctly when using Low speed.

6.06.0

18/02/2022

PMS compatibility: 1.25.0

New features:
1- Scania EMS2 S8 Urea/DEF level added to delta alarms.
2- PMS function: block breaker in closed position when one or two faults occur added (menu 8860 and 8870).

Finetuning:
1- TDU can now show the DEF level when Scania EMS2 S8 is used as engine I/F.
2- 32-bit EIC values is shown on new modbus (function 4, reg 26000).
3- IOM works with all supported engine protocols.
4- AMF Overlap is working when modeshift is used.

6.05.0

01/02/2022

PM compatibility: 1.24.2

New features:

  • Added supported ECU types.
  • NTP Support added.
  • Option A20: An external clearing time setting has been introduced in "Advanced Protection" under "Trip parameters".
  • Option A20: Sunspec model 707 and 708 now supported.
  • Option A20: Sunspec model 709 and 710 now supported.
  • Option A20: Sunspec model 703 now supported.
  • Option A20: Sunspec model 704 now supported.
  • Option A20: Sunspec model 705 now supported.
  • Option A20: Sunspec model 711 now supported.
  • Option A20: Q(U) VRef available in the DU-2, TDU and USW data tracer and trending.
  • Option A20: Sunspec model 702 now supported.
  • Option A20: Ability to disable option A20 functionality using menu 9101.
  • Option A20: Sunspec model 701 supported.
  • Option A20: Voltage ride through detection, regulation and protection (based on evaluation of cumulative time).
  • Option A20: Voltage ride through; Suspend regulation drop out time.
  • Option A20: Q(U): Autonomous adjusted VRef is now reset when the DG becomes parallel, when autonomous adjust is enabled, when Q(U) is enabled and when regulation mode is changed over to Q(U).

Changes:

  • Droop curve 1 now uses a more accurate busbar frequency measurement when configured for P(f) operation.
  • Option A20: Fixed cosphi setpoint resolution increased with a factor of 10. Backwards compatibility is not maintained.
  • Option A20: Q(U) open loop time response parameter can now be edited in 10th of a second.

Corrections:

  • No ASC-4 PV irradiance sensor, could make AGC DG's provide inadequate power for mains power export.
  • Cosphi superior setpoints now work with only PV or Battery units on the busbar together with a AGC mains.
  • Volt var handling relative to Vref changed according to tech spec, esp. Autonomous Adj. Vref.
  • Time constant for Vref incorrectly interpreted as open loop time response.
  • When setting parameter #1204 Freq trip type to 'L1 and L2 and L3', the busbar frequency alarms would end up using the generator measurement.
  • Increased measurement inaccuracy at changing frequency could be seen infrequently.

6.04.3

16/11/2021

PM compatibility: 1.24.1

Corrections:

  • Simulating grid frequency via multi-input for droop curve 1 was off by a factor of 10.
  • A change to a different configuration than application 1 using the USW would not persist past a powercycle of the controller.

6.04.2

10/11/2021

PM compatibility: 1.24.1

Corrections:

  • Minimum load was not respected when using droop curve 1.

6.04.1

22/10/2021

Not UL approved version

PM compatibility: 1.24.1

Corrections:

  • Island ramping when loadsharing over CAN or analogue line now works again.
  • Fixed an issue with the EEPROM storage layout.
  • Changing application configuration with jump menu #9160 would not be stored in longterm storage.
  • If the ground relay was enabled and the application configuration was a non PMS single DG, the GB would not open when deloaded.

6.04.0

07/10/2021

Not UL approved version

PM compatibility: 1.24.1

New features:

  • New EIC measurement area included with data validation.
  • Support new J1939 priority for exhaust temperatures (CAT).
  • Extended #1230 G f> 3 and #1260 G f< 3 timers to 2000.0 [s].
  • Power ramps improved. 6- Feedforward control to suppress frequency and voltage disturbances in fixed power, reactive power control (in LFSM situations).

Changes:

  • S nominal import/export set points are obsolete. Both are replaced by one S nominal per measurement area.
  • Maximum timer extended to 3200.0 s on a number of protections (AC, digital inputs, MPU, EIC).

Corrections:

  • Translation now works even though no DU-2 is mounted AND only new language is written.
  • Deload TB before GB opens function works correctly in PEAK SHAVING.
  • PMS priority change via M-Logic or Modbus now works correctly.
  • df/dt now operates on the mains side measurements.

6.03.1

13/09/2021

Not UL approved version

PM compatibility: 1.24.1


Corrections:

  • Freeze regulation during FRT now working correctly.

6.03.0

15/07/2021

Not UL approved version

PM compatibility: 1.24.1

New features:

  • Two new General Purpose PID´s (GP-PID) 5 and 6 are added. Also added new parameters for all GPIDs (1 to 6) to configure the regulator set point.
  • Support of 3 x 2 A/Os on IOM 220/IOM 230 for GP-PID 1 to 6 is added.
  • Support for John Deere Stage V EIC protocol is added.

Changes:

  • TCP/IP security update.

Corrections:

  • Limit events are added in M-Logic for Extended M-Logic Alarms.
  • "Fuel optimization" and "Fuel optimization + running hours" is now working when using percent values.
  • TDU is now able to change to BLOCK mode (requires TDU version 1.3.7.0).
  • Short circuit supervision (option T1) now includes PV and battery units connected (requires ASC-4 version 4.17.0).
  • EIC transmission rate stability is improved.
  • Default IP address is changed from 192.168.2.2 to 192.168.2.21 to match the TDU default address.

6.02.1

06/05/2021

UL approved version

PM compatibility: 1.23.0

Corrections:

  • Plant management Group Tie redundancy is improved in AUTO and ISLAND plants to secure groups without a start signal to start and stop properly when in need of a redundant unit.
  • Corrected the text for IP, subnet, gateway.
  • Corrected that alarm and battery logs where not shown correctly when the number of entries reached maximum.

6.02.0

06/04/2021

Not UL approved version

PM compatibility: 1.23.0

New features:

  • Support for FPT + Iveco Stage V EIC protocol is added.
  • Four new M-Logic alarms with extended delay are added in menu 3620-3650.
  • VDE 4110 support with MAINS unit in power management is added.
  • Event log entry is added when application setup changes.
  • Support of DVC 550 PSS is added.
  • New GOV and AVR step test are added in parameter group #2970.

Changes:

  • CIO alarms are added to Modbus.
  • Minimum set-point is lowered to 10% for low AC voltage alarms.

Corrections:

  • QSK60G EIC auto view is showing correct values.
  • DVC 550/D550 communication when EIC and Ext. Modules DEIF protocols were selected on two CAN ports is corrected.

6.01.2

15/03/2021

Not UL approved version

PM compatibility: 1.22.0

Corrections:

  • The 4-20 mA output of the option EF5 analogue card now works again.
  • Power factor set point on Modbus is now correctly initialized after a power-up.

6.01.1

12/02/2021

Not UL approved version

PM compatibility: 1.22.0

Corrections:

  • Corrected an issue that caused a mains controller to not be able control the PF setpoint (superior cos phi) on genset controllers.
  • N+X now works when Fuel optimisation is in use.
  • Priority update now works when more than 16 gensets or more than 16 mains are present in a plant configuration.
  • PMS priority data is correct maintained internally in all genset controllers.
  • Breaker feedbacks are properly updated on the I/O status and the I/O setup page.

6.01.0

11/01/2021

UL approved version

PM compatibility: 1.22.0

New features:

  •    Added support for Yuchai Diesel+Gas J1939 protocols.
  •    Addded support for Weichai Diesel+Gas J1939 protocols.
  •    Added support for MAN J1939 protocol.

6-00-0

07/01/2021

Not UL approved version

PM compatibility: 1.22.0

   - Initial release.

On this page, you can download software updates for your product(s) and help yourself to various utility tools and add-ons that will assist you in setting up, detecting faults and configuring your product(s).

Please be advised that not all of our products can be updated by the user. Nor do all of our products come with a utility tool. Consequently, the list on this page cannot be considered an overview of our product programme.

DEIF will register your download along with the used e-mail address for the purpose of sending out information on future updates, if requested.

DEIF cannot be made responsible for any consequences of failed product updates or use of utility tools. Nor can DEIF A/S be made responsible for consequences of changes in behaviour of products due to a software upgrade. It is always the responsibility of the user to ensure correct set-up and configuration before commissioning. Please study the version log of the software before updating the product.

Licence agreement for software downloaded from www.deif.com

Downloaded software remains the property of DEIF. The software may not be distributed for commercial purposes, changed or reused in full or in part or sold to any third parties.

The latest versions for full functionality

As always, we recommend that you install our offered improvements to fully utilise your DEIF product.

All improved software can be downloaded at your convenience at www.deif.com under “Software”.

Should you have any questions or experience problems finding the relevant software for your product, please feel free to call DEIF A/S at +45 96149614 or your relevant local DEIF office. Alternatively, we are always ready to assist you, if you send an e-mail to support@deif.com.