The GPM5∙1 module is a class 0.5 grid measurements and protection module, fully configurable from the main application. The module has an onboard processor for sampling of grid measurements such as three-phase voltages, currents, phase angles and power vector measurements. The availability of these measurements/calculations as variables takes load from the application, thus making it faster. The GPM5∙1 module enables the application to read the following values directly from the process image, thus reducing the processing time of the application.

A special feature of the GPM5∙1 card is that it has a true class 0.5 calculation, also on power measurements. The module features class 0.5 measurements of voltage, frequency, current, power, reactive power and phase angle

Inputs 

  • 2 x direct three phase voltage inputs (L1, L2, L3, N)
  • Input range: 0 to 690 V
  • Measure range: 40 to 690 V
  • Frequency: 40 to 70 Hz
  • Load max.: 0.5 mA or 0.3 VA per phase
  • Overload: 130 % continuously, 200 % for 10 s
  • External fuse, maximum 2 A slow-blow
  • UL/cUL: Maximum 600 V L-L, above 2000 m altitude maximum 520 V

  • 1 x direct three phase current input (L1, L2, L3) 
  • Input range: 0 to 1 or 0 to 5 A
  • Frequency: 40 to 70 Hz
  • Load max.: 0.4 VA per phase
  • Overload: 20 A for 60 s, < 75 A for 10 s, < 300 A for 1 s
  • UL/cUL: From listed or R/C (XODW2.8) current transformers

Outputs

  • 2 x digital relay outputs (normally open) with feedback supervision
  • 24 V, maximum 1 A resistive

Certification class

  • 0.5 measurement of voltage, frequency, current, power, reactive power, phase angle.

Galvanic separation

  • 3.25 kV 50 Hz isolation between voltage measurement inputs individually and between voltage measurement inputs and all other potentials.
  • 550 V 50 Hz isolation between relay outputs, digital inputs (feedback supervision) and all other potentials.

Safety

  • Installation (over-voltage) category III, 600 V, pollution degree 2.

  • EN 61010-1 tested at 50 Hz, 60 s.
  • Each galvanic group tested to other galvanic groups and to Protective Earth, PE.

Accuracy

  • 0.5 % at reference temperatures
  • 1.0 % at operational temperatures
  • IEC 60688

Size

  • 6 TE (30.48 mm)

Power consumption

  • Maximum 4 W