The IFM5∙1 interface and fieldbus module offers RS-485/422, SSI and CAN interfaces.

2 RS-485/422 interfaces 

  • Standards: TIA/EIA-485 ANSI/TIA/EIA-422-B
  • Baud rate: 9.6, 19.2, 38.4, 57.6, 115.2, 230.4, 460.8 or 921.6 kbit/s
  • Word length: 5, 6, 7 or 8 bits
  • Parity: None, even, odd, mark or space
  • Stop bits: 1 or 2
  • Flow control: None
  • Biasing: On or off
  • Communication lines: 4 wire full duplex or 2 wire half duplex
  • Isolation: Optically isolated from other potentials, 550 V 50 Hz.

2 CAN interfaces

  • Standards: ISO 11898
  • Baud rate: 20, 50, 125, 250, 500, 800 or 1000 kbit/s sample point at 80 to 87.5 %
  • Isolation: Optically isolated from other potentials, 550 V 50 Hz.

2 SSI interfaces

  • Standards: Synchronous Serial Interface, SSI, Stegmann Interface ANSI/TIA/EIA-422-B
  • Baud rate: 125, 250, 500, 1000, 1250 or 1500 kbit/s
  • Word length: 8 to 32 bits
  • Data delay: Configurable: 0.04 to 50 ms
  • Coding: Binary or Gray code
  • Frame error suppression: Yes or no
  • Isolation: As a group, SSI is optically isolated from other potentials, 550 V 50 Hz.
  • SSI device supply: 24 V, maximum 100 mA per channel/device.
  • SSI power supply: input 18 to 36 V, maximum 1 A

Size

  • 6 TE (30.48 mm)

Power consumption

  • Maximum 4 W
 

AWC 500 support

Lasse Vejrup, Department Manager

+45 3010 3171 |